The Supporting Cast: Auto-Reclosing, Synchro-check, Breaker Failure and the Fault Locator

The Supporting Cast: Auto-Reclosing, Synchro-check, Breaker Failure and the Fault Locator
After the trip, another job begins: restoring service safely, confirming the breaker opened and locating the fault.
Part 8 of 10⏱ 4 min readLevel: Intermediate
🎯 What you will learn in this part
  • Auto-reclosing and its modes
  • Synchro-check and voltage protection
  • Breaker failure, thermal overload and the fault locator

Automatic reclosing (AR)

Experience shows that about 85% of arc faults on overhead lines extinguish themselves after the protection trips, so the line can be reclosed. Reclosing is permitted on overhead lines only; if the protected object is mixed (an overhead line with a transformer or cable), reclosing must be ensured only for faults on the overhead section.

  • After single-pole, three-pole or both kinds of tripping, with a single shot or several (up to 8 reclosing attempts).
  • Separate action times for each attempt, or none.
  • Separate dead times after single-pole and three-pole tripping, for the first four attempts.
  • Optional pickup-controlled start with separate dead times after single-, two- and three-phase pickup.
  • Optionally adaptive dead time, phase-to-phase voltage and reduced dead time.
  • It can work with an external reclosing device, or the internal function can be started by an external protection.

Synchronism and voltage check

Before reclosing after three-pole tripping the device checks synchronism: fast measurement of the voltage difference Udiff, the phase angle difference φdiff and the frequency difference fdiff. There is also an alternative dead-line / dead-bus check. Switching under asynchronous conditions is possible with advance calculation of the synchro-time, with minimum and maximum voltage and separate criteria before manual closing of the breaker.

Voltage protection (optional)

TypeStages
Overvoltage phase-to-earthTwo stages, common time delay
Overvoltage phase-to-phaseTwo stages, common time delay
Positive sequenceTwo stages, each with a time delay
Negative sequenceTwo stages, each with a time delay
Zero sequence or any single-phase voltageTwo stages, each with a time delay
Undervoltage phase-to-earth or phase-to-phaseTwo stages, common time delay
Undervoltage positive sequenceTwo stages with a settable current criterion

Breaker failure (50BF)

The function provides rapid backup clearance if the breaker fails to respond to a trip command. When a trip command is issued, a timer T-BF starts and runs as long as the command is present and current keeps flowing in the breaker poles. If the breaker opens, the current stage resets quickly (typically 10 ms) and stops the timer; otherwise a trip command goes to the backup breakers.

  • Independent current stages monitoring current flow in each pole.
  • Independent monitoring times for single-pole and three-pole tripping.
  • Start by a trip command of any internal protection function or by external trip functions.
  • One or two stages, with short drop-off and overshoot times.

The fault locator

An independent function with its own measured-value memory and dedicated filter algorithms. Fault current and voltage pairs (at intervals of 1/20 of an AC cycle) are stored in a circular buffer and frozen shortly after the trip command, before the measured values are distorted by the breaker opening. The result is shown in ohms, kilometers, miles or as a percentage of line length, with parallel-line compensation, and with consideration of load current for single-phase earth faults fed from both sides. It can also be output as a BCD code or an analog value.

Thermal overload protection

It models heating caused by the ohmic losses of the protected object (especially cables), using true RMS measurement of the three phase currents, with settable thermal and current alarm stages.

✅ Key Takeaways
  • Auto-reclosing is for overhead lines only, up to 8 attempts, with several dead times.
  • Synchro-check examines Udiff, φdiff and fdiff, or dead-line / dead-bus.
  • 50BF protects on breaker failure with the T-BF timer and current monitoring.
  • The fault locator is independent and displays ohm, km, mile or percent.
🧠 Test yourself (click a question to reveal the answer)
Where may automatic reclosing be used?
On overhead lines only.
What quantities does synchro-check examine?
Voltage difference, phase angle difference and frequency difference.
What stops the T-BF timer?
The current stage resetting after the breaker opens.
Source: Siemens manual "SIPROTEC Distance Protection 7SA6" (C53000-G1176-C156, Siemens copyright 2000 and 2002). This article is an educational explanation in the author's own words; values are for guidance only, so check the manual for your installed version before any design or setting. This blog is not affiliated with Siemens. SIPROTEC and DIGSI are trademarks of their owners.