Fibre Between Line Ends: Protection Data Interface and Two- and Three-End Topologies

Fibre Between Line Ends: Protection Data Interface and Two- and Three-End Topologies
7SA6 devices at the two ends of a line talk to each other directly. Meet the communication channels and how they are supervised.
Part 6 of 10⏱ 4 min readLevel: Advanced
🎯 What you will learn in this part
  • Communication topology for two- and three-end lines
  • Fibre-optic modules and distances
  • Channel supervision and what happens when it fails

One device at each end

The devices at the ends of the protected zone exchange measuring information through protection data interfaces using dedicated communication links (usually fibre optic) or a communication network. Through this interface go teleprotection data and other signals such as closing the local breaker, external trip commands and binary information.

LineInterfaces required
Two-end lineOne interface, PI 1, in each device.
Three-end line (teed feeder)At least one device with two interfaces, PI 1 and PI 2, to form a communication chain.

The number of devices (address 147 NUMBER OF RELAY) must equal the number of ends, and only current-transformer sets that bound the protected object are counted. Device indexes do not have to match the order of the chain, and it does not matter which interface connects to which.

Communication media

Communication runs over direct optical fibre or communication networks. For short distances a direct connection at 512 kbit/s is possible; for longer ones communication converters such as X21 or G703.1 are recommended, and modems and communication networks can also be used. Protection tripping times depend on transmission quality and operating time.

ModuleFibre typeWavelengthTypical distance
FO5Multimode 62.5/125 µm820 nm1.5 km
FO6Multimode 62.5/125 µm820 nm3.5 km
FO7Monomode 9/125 µm1300 nm10 km
FO8Monomode 9/125 µm (FC connector)1300 nm35 km
⚠️ Mind redundancy
For ring topologies the devices connected to the communication network must be truly separated: do not route different lines through the same multiplex card, as there would be no alternative line if the card failed.

What is transmitted?

  • Measured values from all ends of the protected object.
  • 4 commands to all remote ends.
  • 24 additional binary signals to all remote ends.
  • Teleprotection scheme data.

Channel supervision

The communication is monitored continuously. Occasional faulty telegrams are not a direct risk; they are counted and stored as statistics. If several faulty or no telegrams arrive and the data-disturbance alarm delay (default 100 ms, configurable) is exceeded, an alarm is output. If the system offers no alternative path (as with a ring topology), the teleprotection scheme is disabled and returns automatically when transmission is healthy.

The device also detects and corrects operating-time jumps (for example from switching inside the communication network) and measures the times again after at least 2 seconds. If communication is interrupted for longer than a settable period it is treated as a transmission failure with a corresponding alarm. During commissioning the device shows the magnitude and phase angle of local and remote values, the transit time and the availability of the channel.

💡 A rule of thumb
During commissioning, check the communication topology first (section 8.3.5 of the manual) before testing teleprotection schemes.
✅ Key Takeaways
  • A two-end line needs one interface per device; three ends need at least one device with two.
  • Direct fibre runs at 512 kbit/s, with communication converters for longer distances.
  • FO5 to FO8 modules cover from 1.5 km to 35 km.
  • The channel is supervised continuously; the scheme is disabled on failure and restored when healthy.
🧠 Test yourself (click a question to reveal the answer)
How many interfaces does a three-end line need?
At least one device with two interfaces, to form a communication chain.
What is the speed of a direct fibre connection?
512 kbit/s.
What is the longest typical distance in the manual?
35 km, with the FO8 module and monomode fibre.
Source: Siemens manual "SIPROTEC Distance Protection 7SA6" (C53000-G1176-C156, Siemens copyright 2000 and 2002). This article is an educational explanation in the author's own words; values are for guidance only, so check the manual for your installed version before any design or setting. This blog is not affiliated with Siemens. SIPROTEC and DIGSI are trademarks of their owners.