- Communication topology for two- and three-end lines
- Fibre-optic modules and distances
- Channel supervision and what happens when it fails
One device at each end
The devices at the ends of the protected zone exchange measuring information through protection data interfaces using dedicated communication links (usually fibre optic) or a communication network. Through this interface go teleprotection data and other signals such as closing the local breaker, external trip commands and binary information.
| Line | Interfaces required |
|---|---|
| Two-end line | One interface, PI 1, in each device. |
| Three-end line (teed feeder) | At least one device with two interfaces, PI 1 and PI 2, to form a communication chain. |
The number of devices (address 147 NUMBER OF RELAY) must equal the number of ends, and only current-transformer sets that bound the protected object are counted. Device indexes do not have to match the order of the chain, and it does not matter which interface connects to which.
Communication media
Communication runs over direct optical fibre or communication networks. For short distances a direct connection at 512 kbit/s is possible; for longer ones communication converters such as X21 or G703.1 are recommended, and modems and communication networks can also be used. Protection tripping times depend on transmission quality and operating time.
| Module | Fibre type | Wavelength | Typical distance |
|---|---|---|---|
| FO5 | Multimode 62.5/125 µm | 820 nm | 1.5 km |
| FO6 | Multimode 62.5/125 µm | 820 nm | 3.5 km |
| FO7 | Monomode 9/125 µm | 1300 nm | 10 km |
| FO8 | Monomode 9/125 µm (FC connector) | 1300 nm | 35 km |
What is transmitted?
- Measured values from all ends of the protected object.
- 4 commands to all remote ends.
- 24 additional binary signals to all remote ends.
- Teleprotection scheme data.
Channel supervision
The communication is monitored continuously. Occasional faulty telegrams are not a direct risk; they are counted and stored as statistics. If several faulty or no telegrams arrive and the data-disturbance alarm delay (default 100 ms, configurable) is exceeded, an alarm is output. If the system offers no alternative path (as with a ring topology), the teleprotection scheme is disabled and returns automatically when transmission is healthy.
The device also detects and corrects operating-time jumps (for example from switching inside the communication network) and measures the times again after at least 2 seconds. If communication is interrupted for longer than a settable period it is treated as a transmission failure with a corresponding alarm. During commissioning the device shows the magnitude and phase angle of local and remote values, the transit time and the availability of the channel.
- A two-end line needs one interface per device; three ends need at least one device with two.
- Direct fibre runs at 512 kbit/s, with communication converters for longer distances.
- FO5 to FO8 modules cover from 1.5 km to 35 km.
- The channel is supervised continuously; the scheme is disabled on failure and restored when healthy.