The Complete Guide to SIPROTEC 5 Compact (7SX800): Everything from Concept to Commissioning and Analysis

عنوان المقال
Everything you need to know about SIPROTEC 5 Compact in one article: from concept and functions to engineering, testing and analysis.
Complete reference⏱ about 35 min readLevel: beginner to advanced

This is the reference that gathers the whole series in one place, for readers who prefer long, continuous reading. It holds the ten parts in order, then a reference table of functions by ANSI number, a glossary and a FAQ. Jump to any part from the index. If you prefer reading in installments, the series is also published as separate articles (links at the end).

1/6 × 19″
Device width
4 + 4
Current + voltage inputs
3
Binary I/O variants
7
Ready-made templates
Part 1 of 10

7SX800: The Compact Relay That Plays in the Big League – A Complete Overview of SIPROTEC 5 Compact

What exactly is SIPROTEC 5 Compact?

SIPROTEC 5 Compact (model 7SX800) is a universal protection device from Siemens. It belongs to the SIPROTEC 5 family but comes in a compact housing. It targets medium-voltage networks, industry and infrastructure first, and can also be used in low- and high-voltage applications.

The core idea is simple: one device instead of many models. Its function changes through the application template and through the functions you enable with Function Points. That means fewer models in stock, and lower training and spare-part costs.

1/6 × 19″
Housing width
4 + 4
Current + voltage inputs
4 / 14 / 17
Binary inputs per variant
2.2 M+
SIPROTEC devices in service (per the catalog)

Three pillars behind the device

PillarWhat it means in practice
From SiemensOver 100 years of protection experience, certified development and production, and the same SIPROTEC 5 algorithms inside a compact housing.
For the futureVirtual testing through SIPROTEC DigitalTwin, IoT connectivity for faster response, and built-in cybersecurity.
For youA universal device with few models, a display that shows the single-line diagram, and high I/O density for small panels.

Where is it used? The main applications

  • Feeder and overcurrent protection at all voltage levels: radial networks, open or closed rings, and lines fed from one or both ends.
  • Protection of small and medium motors (100 kW up to 2 MW).
  • Voltage and frequency protection, and load shedding.
  • Protection and grid connection of renewable infeeds (decoupling).
  • Ground-fault detection in isolated or arc-suppression-coil grounded networks.
  • Backup protection for differential protection of lines, transformers, generators, motors and busbars.
  • Protection and monitoring of double-star capacitor banks, power-quality monitoring, and retrofit projects.

Quick specifications

ItemValue
Current / voltage inputs4 / 4
Binary inputs (BI)4, 14 or 17
Binary outputs (BO)5, 11 or 8
DisplayColor graphic, 320×240 pixels
Function keys / LEDs9 keys / 8 two-color LEDs
Power supplyDC 24 to 250 V or AC 100 to 230 V
MountingFlush-mounting, or surface-mounting with a mounting frame
ExpandabilityHardware is not modular (not expandable)

The seven application templates

When you create a project in DIGSI 5 you pick a ready-made template that holds the basic settings and the required functions, then add or remove whatever you like. The available templates:

No.Template
1Non-directional overcurrent (definite/inverse time), 4×I measurement
2Non-directional overcurrent, 4×I and 4×V measurement
3Directional overcurrent, grounded network
4Directional overcurrent, compensated or isolated network
5Motor: current measurement
6Motor: current and voltage measurement
7Decoupling (grid disconnection)
💡 Tip before ordering
Register on Industry Mall to use the SIPROTEC 5 configurator: it automatically stores your last 50 configurations, saves the function-point calculation, and lets you add comments such as the feeder name.
✅ Part 1 takeaways
  • 7SX800 is a compact universal protection device (1/6 × 19″), aimed mainly at medium voltage.
  • One device + templates + function points = fewer models and lower costs.
  • Three variants for binary I/O, and in all of them 4 current and 4 voltage inputs.
  • It combines protection, control, automation, monitoring, communication and cybersecurity.
Part 2 of 10

Feeder Armor: Overcurrent (50/51), Directional (67) and Auto-Reclosing (79) Step by Step

50/51 and 50N/51N: the foundation

Non-directional protection is suitable as main protection in radial networks fed from one end and in open rings, and as backup protection on lines and transformers (with transformers, the preferred use is backup for the sections downstream).

The device comes preconfigured with two definite-time stages and one inverse-time stage. You can add further definite-time stages and one stage with a user-defined characteristic.

What does each stage offer?

  • Blocking by a binary input or by other functions (inrush detection, auto-reclosing, cold-load pickup detection).
  • Stabilization against false pickup caused by transformer inrush currents.
  • Operation as an alarm-only stage with no trip.
  • Measurement of the fundamental component or the RMS value.
  • Ground stages use calculated 3I0 or the measured ground current.
  • An independent dropout time per stage.
CurveANSI/IEEEIEC
Inverse✔✔
Moderately inverse✔–
Very inverse✔✔
Extremely inverse✔✔
Fully inverse✔–

Directional 67/67N: when current magnitude is not enough

On parallel lines with a single infeed, cables fed from both ends and ring networks, knowing the fault-current magnitude is not enough; you must know the direction of power flow toward the fault. The same preconfigured stages are available, with the direction settable per stage, a rotatable direction characteristic for phase protection, and a freely settable direction for the ground function.

⚠️ Watch out for loss of measuring voltage
Directional functions depend on voltage, so their stages can be blocked on measuring-voltage failure through the 60FL function, to avoid a false trip when a VT fuse blows, for example.

Directional comparison: faster fault isolation

On lines fed from both ends, the devices exchange direction information so each one isolates the faulty section quickly instead of relying on long time grading. The exchange runs over IEC 61850 GOOSE messages or over pilot wires, and you can implement either a release scheme or a blocking scheme.

💡 GOOSE instead of wires
Replacing signal wiring between devices with GOOSE messages cuts copper cabling and simplifies later changes, but it requires careful communication-network planning (covered in Part 7).

Fast tripping when closing onto a fault

  • 50HS: instantaneous tripping when closing onto a faulty line if the fault current is high (two stages at most). When used on a transformer, set it above the maximum through-fault current or inrush current.
  • SOTF: for applications where 50HS is not enough; it trips instantaneously even with low fault currents. It has no measurement of its own and is tied to the pickup of another function, such as an overcurrent stage.

51V: voltage-restrained overcurrent

It comes in three forms: Controlled, Voltage-dependent (the pickup current decreases linearly as voltage drops) and Undervoltage stability. The last form is common in generator protection: on a nearby fault the excitation voltage collapses and the short-circuit current falls below the pickup value, and the feature keeps the pickup alive. A fuse-failure monitor prevents false operation.

How does it avoid being fooled by transformer inrush?

When a transformer is energized, a magnetizing inrush current flows that can reach several times rated current and last from tens of milliseconds to several seconds. Inrush detection uses two methods: harmonic analysis and current-waveform analysis (CWA). They can run together with OR logic, a "1-out-of-2" decision, for higher availability. The result is a blocking signal for the affected functions, so you can set them more sensitively.

Breaker failure 50BF

Two stages provide backup protection for phases and ground if the main breaker fails to clear the fault: a retrip or a trip command to the busbar. Breaker operation is verified by current measurement and by the breaker position contact, with phase-segregated current detection. The function can be started by any internal protection function, a binary input or a GOOSE message, and for higher dependability two binary inputs can be used in parallel for the external start.

Automatic reclosing (79)

The document notes that about 85% of arc faults on overhead lines extinguish themselves after the trip, so service is restored by automatic reclosing. The function supports trip-controlled or pickup-controlled start, three-pole reclosing, several shots (multi-shot), different dead times by fault type, and cooperation with synchrocheck. Overcurrent settings can also change dynamically depending on the reclosing state.

Supporting functionThe idea
DLC (Dead-line check)Reclose only when the line is dead, when synchrocheck cannot be used.
ADT (Adaptive dead time)The adaptive dead time is used only if reclosing at the remote end succeeded, to reduce stress on equipment.
RDT (Reduced dead time)Shortens the dead time based on remote-end voltage when faults in the overreach zone beyond the protected line are cleared, without teleprotection.

Trip-circuit supervision and lockout

The 74TC function supervises the breaker coil and its wiring through two binary inputs and raises an alarm when the circuit is interrupted. The 86 (lockout) function is available in all templates.

🔧 From real design work
Trip-circuit supervision uses two binary inputs, and variant V1 has only 4. Count your inputs (breaker status, disconnector, earthing switch, 74TC, external start for 50BF…) before choosing the variant.
✅ Part 2 takeaways
  • Overcurrent: two definite-time stages plus one inverse stage preconfigured, with IEC and ANSI curves.
  • Directional protection is essential for parallel lines, two-end infeed and rings, and can be accelerated with GOOSE-based directional comparison.
  • Inrush restraint, SOTF, 50HS, breaker failure and auto-reclosing complete the armor.
  • Plan your binary inputs early (74TC alone needs two).
Part 3 of 10

Hunting Hidden Ground Faults: The Secrets of Sensitive Ground-Fault Protection (67Ns)

Why is a ground fault a special challenge?

In networks with an isolated neutral or one grounded through an arc-suppression coil, a ground fault does not produce a large current as a phase-to-phase fault does, so you need functions designed for high sensitivity and direction determination. 7SX800 offers two main functions: 50Ns/51Ns, non-directional, and 67Ns, directional. Both offer more than one measuring method that can run in parallel to suit the operator's philosophy and the shape of the fault.

The detection toolbox

MethodThe ideaWhere it helps
3I0> and V0>Measure the residual current or residual voltage; the faulted phase can be identified when phase voltages are connected.Initial detection and backup protection.
cos φ (watt-metric)Determines the direction of a stationary fault from the active component of the current.Compensated (coil) networks.
sin φ (var-metric)Determines the direction from the reactive component.Isolated networks.
φ(V,I)The angle between the ground current (corrected for angle error) and the rotated V0 voltage.An alternative to cos/sin if it suits the operator's philosophy.
Harmonics (3rd, 5th or 7th)Determines direction from the phase angles of V0 and 3I0 harmonics.Locating stationary faults, especially in medium-voltage rings with open points.
TransientWorks in the first 1 to 2 periods by evaluating the active energy of the transient process.Faults that extinguish quickly (half a period to several periods), meshed networks and closed rings.
Pulse patternSwitching a capacitor in parallel with the coil produces a pulsating current, so the function finds the faulty feeder by the pulse pattern.Overcompensated networks.
Admittance Y0>An admittance stage within the 67Ns function.Applications that call for this kind of measurement.

In addition to these methods, a simple non-directional ground-current stage can be enabled when needed.

The intermittent ground fault

An intermittent fault arises from weakened insulation in cables or from water ingress into cable joints; it may extinguish itself or develop into a permanent short circuit. During it, neutral resistors may suffer thermal stress in low-impedance networks, and ordinary ground-fault protection cannot detect the short current pulses. The device's answer is to sum the individual pulses over time and trip when an adjustable total time is reached, evaluating RMS values relative to one period. A directional version is also available.

⚠️ Beware of message flooding
Stationary-fault detection functions such as cos φ may react to an intermittent fault and flood the logs and fault records with messages. The device avoids this by blocking them automatically during an intermittent fault.

A dedicated ground-fault log

The device keeps a ground-fault log separate from the ordinary fault log: up to 10 ground faults, with up to 100 messages per fault. That way ground-fault details are not lost among other protection messages.

A sensitive current transformer when needed

The current terminal (8 poles with four integrated transformers) comes in two versions: 4 protection transformers, or 3 protection + 1 sensitive transformer. The type can be exchanged later on site, for example from sensitive to normal when the grounding system changes.

87N: restricted ground-fault protection and the neutral point

Longitudinal differential protection can miss ground faults close to the neutral of a solidly or low-impedance grounded star winding, and 87N (restricted ground-fault protection) fills that gap: it evaluates the neutral-point current together with the zero-sequence current calculated from the phase currents, with stabilization that prevents false trips for external faults. It supports autotransformers by selecting the measuring point that gives the largest restraint current. 50N/51N can also be applied to the neutral-point current directly, or as tank-leakage protection on insulated transformers.

📌 Quick fact
The 59N/64 (residual voltage) function measures voltage directly from a broken-delta winding or calculates it from the phase voltages, with the choice of the fundamental component or strong suppression of harmonics and transients.
✅ Part 3 takeaways
  • Ground faults in isolated and compensated networks need 50Ns/51Ns and 67Ns, not plain overcurrent.
  • Pick the method by grounding type: cos φ for compensated, sin φ for isolated, transient for fast faults, harmonics for rings.
  • Intermittent faults are detected by summing pulses over time, and stationary-fault detection is blocked during them.
  • For transformers, 87N covers the neutral-point zone where differential protection is weak.
Part 4 of 10

Guardian of Motors and Capacitor Banks: Smart Thermal Protection from Start-Up to Trip

Motor protection in one device

7SX800 covers small and medium motors (100 kW to 2 MW) through templates 5 (current measurement) and 6 (current and voltage). The advantage stated in the catalog: combining protection and control in one device reduces investment, with complete thermal protection for the motor.

FunctionWhat it protects against
49 stator thermalOverload, cooling problems and contamination.
49R rotor thermalThe rotor during starting, from too many or too long start attempts, or a jammed rotor.
48 starting-time supervisionA start that lasts longer than it should, with different maximum times for cold and hot starts.
66 restart inhibitRestarting the motor if that would exceed the rotor temperature limit.
50L load jamSudden rotor jam, detected faster than thermal protection.
14 locked rotorThe locked-rotor condition.
46 unbalanced loadRotor heating caused by negative-sequence current.
37 undercurrentDetects pumps and compressors running with no load (idling).
38 temperature supervisionWinding and bearing temperatures via sensors.

Why is the rotor the weak point?

In normal operation, even under overload, rotor temperature stays well below its limit. But high starting currents make the rotor, not the stator, the part at risk because of its short thermal time constant. That is why the 66 function blocks a restart when it is clear that the rotor temperature limit would be exceeded in the start attempt, instead of letting the breaker trip after several attempts.

Load jam versus thermal

A rotor jam causes a sudden jump in the phase currents. The thermal protection may also pick up when the thermal model exceeds its values, but the 50L function detects the jam faster, reducing damage to the motor and the driven equipment (gears, bearings and so on).

Unbalanced load 46

It relies on the negative-sequence current and models thermal behavior by integration; the trip curve is inverse, so small unbalanced currents give a longer trip time. The machine constant K lies between 5 and 40 seconds, and a large negative-sequence current (around 10 times the permissible value) is limited to avoid false operation on asymmetrical faults. There is also an alarm when sustained unbalanced load exceeds a threshold after a delay.

Temperature measurement with an external RTD unit

Temperature (windings, oil or bearings) is captured through an external temperature-monitoring device (RTD unit, for example 7XV5662-xAD10), connected to the relay over the dedicated SUP protocol via serial or Ethernet. Supported sensors are Pt 100, Ni 100 and Ni 120, and up to 12 measuring points can be processed with two thresholds each, plus automatic wire-break detection.

Capacitor banks: three specialized functions

FunctionThe idea
59C capacitor peak overvoltageCalculates the peak voltage per phase from the fundamental and harmonics, because rising peak voltage can destroy the dielectric. Time characteristics: inverse IEC/IEEE, user-defined, or independent (up to 4 stages).
60C current unbalanceMonitors with high sensitivity the unbalanced current between the two neutral points of a double-star bank, and allows counting defective elements.
50RS restrike monitoringMonitors the breaker to detect arc restrike after the capacitor bank is switched off, and issues an auxiliary trip.
💡 Function-point budget
Functions 48, 50L and 66 cost 5 function points each. Remember that the point budget is calculated at ordering (we cover it in Part 9).
✅ Part 4 takeaways
  • Motor functions protect both stator and rotor: 49, 49R, 48, 66, 50L and 46.
  • Load jam detects a jam faster than thermal protection, and restart inhibit protects the rotor from repeated starting.
  • Temperature is measured through an external RTD unit with up to 12 points.
  • For capacitors: 59C peak voltage, 60C unbalance and 50RS restrike.
Part 5 of 10

Voltage, Frequency and Power: How 7SX800 Decouples Generation, Protects the Grid and Monitors Power Quality

Voltage protection: 27, 59, 47 and 59N

These functions monitor the permissible voltage range and protect equipment against voltage drops or rises; they also serve decoupling and load-shedding tasks. They come with two stages by default, expandable to three, and undervoltage functions can be blocked by a current criterion.

TypeThe idea
Three-phasePhase-to-ground or phase-to-phase voltages, measuring the fundamental or true RMS.
Positive-sequence voltageTwo-phase or ground faults cause an unbalanced voltage collapse that barely affects positive-sequence voltage, so it suits assessing stability problems.
Any-phase voltage (Vx)For special applications that need a single-phase voltage.
Ferranti compoundingThe capacitive impedance of long lines can raise voltage at the remote end; the remote-end voltage is calculated from local measurements.
dV/dtDetects unsafe conditions caused by imbalance between generated and consumed power, and serves as a load-shedding criterion.
47 and 59NNegative-sequence voltage to monitor voltage unbalance, and zero-sequence voltage to detect ground faults.

24: overexcitation

It detects excessive flux in generators and transformers through the V/Hz ratio: rising voltage causes excessive magnetizing currents, and falling frequency increases losses. It works with one dependent stage using a user-defined curve and two independent stages.

Power: 32, 32R and 37

  • Up to 4 active-power and 4 reactive-power stages, with settable exceed or underrun thresholds, and they can be combined with CFC.
  • 32R for reverse power in generators; the smallest setting is −0.3% of P/Srated, with angle-error correction possible from the transformer test report.
  • 37 for low current or low power, such as pumps running dry.

Applications include detecting negative power, detecting capacitive reactive power on long unloaded lines (where voltage rises), and detecting motors and generators running with no load.

QU: disconnecting generation safely

Q-U protection (directional reactive power with undervoltage criterion) is a grid-code protection at the point of interconnection between a generating plant and the network, to avoid voltage collapse. It detects critical situations and disconnects the source, and it makes sure reconnection happens only when the network is stable. The criteria are adjustable to the BDEW technical directive for generating plants on the medium-voltage network (June 2008) and the FNN specification (February 2010).

📌 Local requirements
The function list also includes voltage protection per the Italian standard CEI 0-16, which reflects the variety of grid codes the device covers.

Frequency: 81, df/dt and load shedding

FunctionStagesNotes
81O overfrequency2 (up to 3)All stages share the same design.
81U underfrequency3 (up to 5)Two measuring methods: angle difference, or filters.
81R rate of frequency changeUp to 5 per typeTwo types: rising and falling df/dt, blocked automatically on undervoltage.
Vector jump (Δφ)—Detects the angular jump of the voltage.
81U load shedding—Accounts for changing infeed conditions due to distributed generation.

Tripping can happen at the local breaker or at the remote end through automatic remote tripping. This group is the basis of template 7 (decoupling).

Synchrocheck and synchronization (25)

When connecting two systems or live equipment to the grid, voltage must be in sync at the instant of closing. The function works in three modes: synchrocheck for galvanically connected networks, connecting synchronous networks, and connecting asynchronous networks while accounting for the breaker closing time. It switches between modes automatically depending on the frequency difference. Depending on the number of voltage inputs, one or two synchronizing points can be applied, with two parameter sets for synchrocheck and up to 6 for synchronization.

PQ-Basic power quality

MeasurementWhat it doesFunction points
Voltage unbalanceV2/V1 and V0/V1 unbalance ratios.20
Voltage variationsDetects voltage dips, swells and interruptions with minimum value and duration.30
THD and harmonicsTHD for current and voltage and their harmonics, with a warning when a limit is exceeded.Within voltage/current packages
TDDTotal demand distortion for currents (3-second value and interval value).10

The nice part is that installed devices can be upgraded with a firmware update and no extra hardware, so you get a quick picture of power quality and spot weak points early. For full assessment per standards such as EN 50160, the catalog recommends dedicated power-quality recorders such as SIPROTEC 7KE85 with the SICAM PQS system.

The fault locator (FL)

The single-ended locator calculates fault impedance and distance, and the result is shown in ohms, miles, kilometers or as a percentage of line length, compensating for the effect of parallel lines and load currents.

✅ Part 5 takeaways
  • Voltage, frequency and power functions are the basis of grid decoupling and load shedding.
  • QU protection disconnects a generating source and prevents reconnection before the network is stable, per BDEW and FNN.
  • Frequency: 81O, 81U, df/dt and vector jump, with special handling of distributed generation.
  • PQ-Basic gives a quick power-quality picture through a firmware update; full assessment needs dedicated recorders.
Part 6 of 10

A Whole Bay in One Device: Control, Automation (CFC), Monitoring and Fault Recording in 7SX800

Control at bay level

The device includes all the control and monitoring functions needed to operate the bay efficiently. The freely configurable color display shows the control diagram, and there are 9 function keys for frequent actions such as starting switching sequences or showing the event list, O and I keys for direct control of equipment, and easy switching of the control authority.

  • The basic control package supports 4 switching objects (breakers, disconnectors or earthing switches), and more objects and sequences can be added with CFC.
  • Protection and control reach the same logical elements, and from the switchgear's point of view they have the same priority.
  • With IEC 61850, interlocking data can be exchanged between bays over GOOSE, so data messages replace wires.

Automation with the CFC editor

The CFC (Continuous Function Chart) editor is a graphical editor for drawing logic diagrams, supported in DIGSI 5 with blocks based on the IEC 61131-3 standard. You connect internal signals, operating states and measured values to logic blocks and process them in real time.

  • Interlockings and switching sequences.
  • Deriving messages or issuing trip commands.
  • Load shedding in the feeder and management of distributed generation.
  • System changeovers according to network state, and automatic network separation on stability problems.
💡 Reuse your work
Parts of a chart can be turned into macros and reused inside the device, the project or other projects. CFC charts can be tested offline without a device and monitored online inside the device.

Monitoring: four groups

GroupScope
Self-monitoringDetecting and storing internal and external faults in secondary circuits.
Grid stabilityFault recorders, continuous recorders and data for control and monitoring centers.
Equipment conditionBreaker statistics (ΣIx, I²t and 2P), SF6 pressure, temperature and others through transducers, and external 20 mA devices.
Power qualityPQ-Basic, as seen in the previous part.

Measurement and recording

The device provides measured values as primary, secondary and reference values, and up to 8 factory-calibrated analog inputs, so no separate measuring transducers are needed. It supports observing signals up to the 50th harmonic for selected functions. Synchrophasors are offered as an option (under development, per the catalog).

1–8 kHz
Sampling rate of the fault recorder
128
Maximum fault records
20 s
Recording of 24 channels at 8 kHz
≈ 890 s
Example: 8 analog channels at 1 kHz, with 6 values and 20 binary channels

Faults are stored in COMTRADE format, with configurable tracks (up to 100 binary tracks and 50 additional measured-value tracks), and the pre-trigger time and storage time are programmable. They are analyzed with SIGRA (covered in Part 10).

Internal logs

LogCapacityPurpose
Operational log2000 messagesOperating and control events (circular).
Fault log1000 messages per fault, up to 128 faultsFault events.
User-specific buffer200 messagesSignals you define.
Ground-fault log100 messages per fault, up to 10 faultsGround faults.
Parameterization history200 messages (cannot be deleted)Every settings change and configuration download.
Communication log500 messagesState of communication links.
Security log500 messages (cannot be deleted)Successful and failed access attempts.
Device-diagnosis log500 messagesMaintenance instructions and internal faults.

Time synchronization: without it, records lose their value

To compare events from devices at different sites, precise synchronization is a must. It is done through IRIG-B, SNTP, the automation-system protocol (such as IEC 61850) or the DIGSI 5 protocol, with accuracy ranging from 1 millisecond to 1 microsecond depending on the source, and events are time-stamped with 1 millisecond resolution. The internal clock has a backup battery, and two timers can be used: primary and secondary, with automatic changeover.

⚠️ A word about the source
The catalog recommends a Meinberg GPS receiver to synchronize all devices through an IRIG-B message. IEEE 1588 synchronization (1 microsecond accuracy) is still under development in this release.
✅ Part 6 takeaways
  • A display with a single-line diagram, 9 function keys and 4 basic switching objects, expandable with CFC.
  • CFC enables interlockings, sequences and load shedding with standard IEC 61131-3 graphical logic.
  • A fault recorder up to 8 kHz and up to 128 records, plus several event logs, some of which cannot be deleted.
  • Time synchronization (IRIG-B/SNTP/61850) is the basis for analyzing faults across more than one device.
Part 7 of 10

The Digital Language of the Bay: Protocols, IEC 61850, GOOSE and Redundancy (RSTP/HSR/PRP)

Built-in ports

PortDescriptionUse
USB-B (front)Protected by a plastic coverThe DIGSI 5 protocol for full device configuration.
Port F electrical2 × RJ45, 100 Mbit/s, up to 20 mEthernet protocols, with or without an integrated switch.
Port F optical2 × duplex LC, 1300 nm, up to 2 km multimode fiberThe same protocols.
Port E (RS485)Serial RJ45IEC 60870-5-103, DNP3 or Modbus RTU, or IRIG-B synchronization.

Several applications can run in parallel on the Ethernet port, and you can switch off what you do not use for security reasons. Protocols are loaded by assigning an "application" to each interface in DIGSI 5.

Supported protocols

ProtocolKey details
IEC 61850Server with reports for up to 6 clients, GOOSE messages, fault records downloaded in COMTRADE format, and reading and changing settings.
IEC 60870-5-104One master or two (redundant), and up to three masters can receive the same information; fault records can be read.
DNP3Serial over RS485 or TCP (up to two masters), with switching commands and fault records.
Modbus TCP / RTUOne master or two redundant; messages, measured values, counters and switching commands.
PROFINET IOWorks as an IO device, with S2 redundancy and an SOE function with a 500-signal buffer.
IEC 60870-5-103Serial, compatible with SIPROTEC 4 and SIPROTEC 5, with freely configurable information maps.
SUPThe Siemens protocol for connecting external temperature or 20 mA units.

GOOSE: when a message replaces a wire

GOOSE is used to exchange messages and values between devices inside a substation and between different substations, and the information is described in standard SCL files (Edition 2). Communication replaces wiring and binary inputs, and the required times are given in the catalog:

< 10 ms
Protection signals
< 20 ms
Switch positions and interlocking
< 100 ms
Measured values and counters

The receiver continuously monitors message arrival, and if communication drops, the missing states automatically move to a safe condition. Messages sent by a device in test mode are ignored by receivers in normal operation, so you can test a device without isolating it from the network.

Redundancy: three technologies

TechnologyThe ideaNotes
RSTPA ring using the switch integrated in the deviceUp to 40 devices in the ring, and up to 30 when mixed with SIPROTEC 4 devices.
HSRThe same message is sent both ways around the ringUp to 50 devices in the ring with a maximum of two RedBoxes; tolerates a single failure (N-1), but evolving faults can cut off part of it.
PRPTwo physically separate networks carry the same messagesHigher availability than HSR, but at double the network-equipment cost.

PRP and HSR follow the IEC 62439-3 standard; the receiver accepts the first message to arrive and discards the second, and if the first never arrives the second is used with no interruption at all. They need no extra parameters, and the maximum number of participants is 512 devices. HSR and PRP can be combined using a RedBox.

💡 Connecting to an external switch
For communication without an integrated switch, the port connects redundantly to the external switch; one port handles the applications and the other is in hot standby, and the switchover takes a few milliseconds.

Additional Ethernet services

  • VLAN (IEEE 802.1q): separates different applications on the same physical medium, improving security, availability and performance.
  • SNTP: synchronization from one or two servers with 1 millisecond accuracy.
  • IEEE 1588 (PTP): 1 microsecond accuracy, but under development per the catalog.
  • SNMP V3: network monitoring for diagnostics only; it does not change values in the device (status "in preparation" in this release).
  • Cloud connection: through GridEdge, to link with platforms such as MindSphere.
⚠️ A security reminder
By default only the DIGSI 5 connection is enabled in the device; all other Ethernet services stay disabled until you enable them yourself. That is exactly what we cover in the next part.
✅ Part 7 takeaways
  • Ports: front USB, Port F electrical or optical, and Port E serial or IRIG-B.
  • IEC 61850 with GOOSE replaces wiring, with under 10 ms for protection signals.
  • RSTP for economical rings, HSR for fast rings with no interruption, and PRP for the highest availability with two networks.
  • VLAN, SNTP, SNMP and IoT services run in parallel and can be switched off when not needed.
Part 8 of 10

Safety First: How 7SX800 Protects People, Equipment and Data (Safety and Cybersecurity)

Safety versus Security: what is the difference?

Safety means protecting people and the primary installation, and Security means protecting against information threats coming from outside. As substation environments open up and grow more complex, traditional mechanisms are no longer enough, so a multi-layer security concept was designed into the device architecture. The catalog states that responsibility for the overall security concept of the system lies with the system operator, while the manufacturer supports it with suitable measures.

Safety in the hardware design

  • Safety CT-Plug: the current transformer terminal is integrated in the connection terminal, so pulling the terminal always short-circuits the secondary, and no open secondary circuits occur when a device is replaced.
  • Fully removable terminals: they ease pre-wiring and replacing the device or modules.
  • No need to open the device to set binary-input thresholds, set the rated current (1 A/5 A) or change the battery.
  • A wide-range power supply common to all components, and cooling that reduces thermal load and extends service life.
  • Calibration data stored inside the measuring modules allows safe replacement or expansion.
⚠️ The classic danger
Opening the secondary circuit of a current transformer during testing or replacement generates a dangerous voltage. The Safety CT-Plug removes this hazard when the terminal is pulled.

Self-monitoring at every level

Device components are monitored continuously: the processor, auxiliary voltage, battery, internal clock, memory, analog inputs, buses and interfaces. Depending on the severity of the fault, a warning is issued, the affected functions are blocked, or the whole device is isolated by opening the life contact. In every case the device-diagnosis log records the cause and the required action.

What is monitored?How?
Analog inputsCurrent and voltage balance and sum, phase sequence, measuring-voltage failure, fast current-sum detection and wire breaks, and plausibility checks at the sample level.
Trip circuit74TC with two binary inputs.
Protection data channels32-bit CRC checks, discarding corrupted telegrams, ignoring sporadic errors and blocking functions on persistent ones, and measuring transit times.
GOOSE messagesCRC check, sequence number, repetition time, and a switch to a safe state on corrupt or test messages.

During engineering, DIGSI 5 also calculates the device load model, so only configurations that are operationally feasible can be loaded.

Cybersecurity: layers of defense

The design relies on standards and regulations such as IEC 62443, IEC 62351, NERC CIP and the BDEW whitepaper, and security starts at the hardware, where encryption keys are stored securely, with hardened communication stacks.

Security goalMeasure in the device
Prevent unauthorized accessRBAC with central user management through RADIUS or Active Directory, with roles per IEC 62351-8 and IEEE 1686, and emergency access when the RADIUS server is unreachable.
Protect communicationAuthentication and encryption with TLS between the device and DIGSI 5, the Web Monitor or the cloud.
PasswordsA connection password of 8 to 30 characters containing upper- and lower-case letters, digits and symbols (NERC CIP compliant), or a confirmation ID for critical actions if RBAC is not enabled.
Reduce the attack surfaceBy default only the DIGSI 5 connection is enabled and all other services are off. IP access can be set per port: full, read-only or no access.
Software integrityDigitally signed firmware files, and security settings stored encrypted.
TraceabilitySecurity events are logged and can optionally be sent to a central server over Syslog, and the security log cannot be deleted.
Block rogue devicesNetwork access authentication per IEEE 802.1x with a RADIUS server.
UpdatesSecurity patch management: a monthly list of Windows updates tested for compatibility with DIGSI 5.
💡 During commissioning
Entering credentials and passwords at every step during setup and testing is not ideal, so full access protection can be switched off until commissioning is finished and then re-enabled for operation.

The Product Security Blueprint and remote access

The catalog recommends an application note numbered SIP5-APP-009 and a security blueprint concept that documents typical configurations, the services and ports used, update procedures, passwords and virus protection. In the recommended design, devices are integrated into optical Ethernet rings through switches, and access from an untrusted external network goes through a gateway that authenticates the user and encrypts the connection (for example over VPN).

✅ Part 8 takeaways
  • The Safety CT-Plug and removable terminals protect people and ease maintenance.
  • Multi-level self-monitoring: warning, then blocking, then isolating the device.
  • Cybersecurity: RBAC, TLS, Syslog, signed firmware and IEEE 802.1x.
  • Secure by default: no service runs except DIGSI 5 until you enable more.
Part 9 of 10

From Panel to Order Code: Hardware, Terminals, Variants and Function Points in 7SX800

The front operating panel

  • A color graphic display with 320×240 pixel resolution.
  • 9 freely assignable function keys, a full numeric keypad, navigation keys and context-sensitive keys.
  • 8 two-color LEDs whose labels appear on the display, plus two status LEDs: green RUN and red ERROR.
  • A front USB-B port protected by a plastic cover.

Any device can be ordered in two mounting styles: flush-mounting, or surface-mounting with the local operating panel using a mounting frame ordered as an accessory, and the frame can be oriented for wiring from above or below.

Terminals: the secret of easy maintenance

  • All terminals can be unplugged individually, which allows pre-wiring and replacing a device without costly rewiring.
  • The 8-pole current terminal has four integrated transformers, in two versions: 4 protection transformers, or 3 protection + 1 sensitive.
  • The 14-pole voltage terminal carries the voltage transformers and the binary input and output signals.
  • Ready-made jumpers connect contacts at a common potential, and the rated current (1 A/5 A) can be changed electronically.

The three variants

VariantBinary inputsBinary outputsNotes
V1451 life contact + 4 fast
V214111 life contact + 10 fast
V31781 life contact + 7 fast

All three have 4 current and 4 voltage inputs and a 1/6 × 19″ width. There is no hardware expansion.

Electrical numbers that matter at design time

ItemValue
Permissible auxiliary voltage rangeDC 19 to 250 V, and AC 92 to 265 V
Rated voltagesDC 24/48/60/110/220 V and AC 100/230 V
Power consumptionAbout 12 W DC, and 42 VA at AC 230 V
Inrush current / recommended protectionUp to 18 A / a 6 A miniature circuit breaker with C characteristic
Stored-energy time on supply lossAt least 50 ms
Voltage inputs0 to 200 V, burden below 0.1 VA, thermal rating 230 V continuous
Binary inputsDC 24 to 250 V, pickup in about 3 ms, consumption 0.6 to 2.5 mA, three threshold ranges
Fast outputs (type F)Typical make time 4 ms (max 5), typical break time 2 ms (max 5), 5 A continuous, 30 A for 1 s, 250 A for 30 ms
⚠️ A note on setting the inputs
A binary-input threshold must be set to the control voltage in use. For time-critical applications with low-active signals, check the dropout times, which depend on cable capacitance; you may need a parallel resistor or a changeover contact.

The order code (MLFB)

The 7SX800 code is made of positions that define: the number of binary inputs/outputs (A, B or C for V1, V2 or V3), the measuring inputs (A: 4 protection + 4 voltage; B: 3 protection + 1 sensitive + 4 voltage), the front-panel version (0 standard, or 1 for the US version), and the Ethernet type (B electrical or C optical).

Function points: pay only for what you need

The main function is set by choosing the device type, while additional functions are chosen at the engineering stage from the function library, provided the required function points do not exceed your balance. More points can be bought at any time.

PackagePoints
Basic package: current functions (50/51, 50N, 79, 50BF, 87N, 49…), RBAC, IEEE 802.1x and recorders0 (Basis)
Voltage-measurement package (27, 59, 67, 81, 25, 32…)30
Motor functions 48, 50L and 665 each
Ethernet protocols (IEC 61850, Modbus TCP, IEC 104, DNP3, PROFINET, RSTP/PRP/HSR)50
Serial protocols (IEC 103, DNP3, Modbus RTU)20
PQ: voltage unbalance / voltage variations / TDD20 / 30 / 10
PQ: 10/12-cycle values / trend / flicker25 each
💡 Worked example
A current-only feeder with IEC 61850: the basic package (0) + the Ethernet package (50) = 50 points. If you add voltage measurement to benefit from the directional functions, the total becomes 80 points. (An illustrative example; check the configurator to confirm.)

License files (DAF) are generated and the points budget is managed through the SIPROTEC Function-Point Manager after registering and creating a budget account. For countries where the manager is unavailable, the device can be ordered preconfigured with 20, 50, 100, 150 or 200 points (codes ZP02, ZP05, ZP10, ZP15 and ZP20).

Accessories worth reviewing

  • The 14-pole voltage terminal, and current terminals (4 protection, or 3 protection + 1 measuring).
  • 2-pole cross-connectors for current and voltage, and terminal covers.
  • The surface-mounting frame, angle rail, USB cover and USB cable for DIGSI 5.
  • SFP RJ45 modules, a Y cable for serial communication, a bus-terminating terminal for RS485, and an adapter cable for IRIG-B.
✅ Part 9 takeaways
  • V1, V2 and V3 differ only in binary inputs and outputs; measurement is fixed at 4 current and 4 voltage.
  • Removable terminals and the Safety CT-Plug make replacement fast and safe.
  • Set binary-input thresholds to your control voltage, and watch dropout times.
  • Function points control what you enable: the basic package is free, voltage is 30, and communication is 50.
Part 10 of 10

From Drawing to Commissioning: DIGSI 5, Built-in Testing, SIPROTEC DigitalTwin and SIGRA

The integrated workflow

Engineering in SIPROTEC 5 Compact is organized around a workflow: from the single-line diagram of the primary system, through ordering, engineering and settings, to testing and commissioning. The catalog divides it into five stages: project definition, device engineering, system engineering, commissioning, and operation and service.

ToolRole
DIGSI 5The configuration, commissioning and operation tool for all SIPROTEC 5 devices.
IEC 61850 System ConfiguratorVendor-independent IEC 61850 substation engineering.
Web MonitorA browser interface for commissioning and monitoring.
SIPROTEC DigitalTwinA cloud virtual twin of the device for testing without hardware.
SIGRAAnalysis of fault records (COMTRADE).
SIPROTEC DashboardA view of the protection fleet through GridEdge and the cloud.

DIGSI 5: everything in one project

In DIGSI 5 all device components and data are managed in one project: topology, devices, setting values, communication settings and process data. You can take the order number (MLFB) from the configurator and create the device with it directly, so engineering starts on a consistent basis.

EditionIn short
CompactFor small projects of up to 8 devices (Compact or non-modular) or one modular device; includes the CFC editor, the device display editor and built-in testing; needs no license key.
StandardNo limit on the number of devices; includes the IEC 61850 System Configurator and single-line and network-topology editors; SIGRA is optional.
Premium with SIGRALike Standard, with flexible IEC 61850 engineering and functional naming, and it includes SIGRA.

The most important DIGSI 5 editors

  • Single-Line Editor: define the initial substation layout with a library of ANSI and ISO symbols, link protection elements to breakers and current and voltage transformers, and take transformer ratios from it automatically.
  • Display Editor: turn the single-line diagram into a device display, with a symbol editor to create your own symbols.
  • Information Routing: an Excel-like routing matrix to link signals to inputs, outputs, LEDs and logs, with powerful filters.
  • Communication Mapping: presets for each protocol that you can edit and copy between devices.
  • CFC: a graphical logic editor with macros, offline testing and online monitoring.

Three ways to view settings

The parameter editor lets you view settings as primary values (so you do not need transformer ratios and avoid conversion errors), as per-unit values, or as secondary values. Protection curves are shown graphically so you can immediately check the effect of your change, parameter groups can be compared in one window, and favorite parameters can be marked for quick display.

💡 Teamwork
Thanks to export and import functions, one team member can set the protection parameters, another the routing and a third the system-interface parameters, and the sections are then merged. DIGSI 5 supports open formats such as IEC 61850 formats and TEA-X.

Test Suite: testing without secondary test sets

  • The built-in test sequencer: you build a test sequence (a short circuit, for example) with up to 6 test items and load it into the device, which simulates the analog and binary inputs in real time.
  • Hardware and wiring test: reading input states, driving contacts and LEDs, and showing measured values on phasor diagrams to find reversed connections, vector-group errors or directionality problems.
  • A wiring test between devices over Ethernet, with no helper needed at the neighboring substation.
  • A loop test for communication links, and finally a protocol test to send chosen values toward SCADA.
  • Offline CFC debugging to test charts before the device arrives.

The result, per the catalog: much shorter testing and commissioning time, documentation of every test performed, and no need for most testing with secondary test sets.

Web Monitor: a browser instead of software

A web interface built into the device that works through the browser, locally or remotely. It helps during commissioning to inspect and compare settings between two devices or against the Siemens default, during inspection to view values with their minimum, maximum and average, and during operation.

IEC 61850 System Configurator

A vendor-independent interactive engineering tool that supports Siemens and other devices and all SCL file types (ICD, IID, CID, SCD, SSD and SED). It supports editions 1, 2.0 and 2.1, and covers GOOSE, reports, system topology, SMV for the process bus, and IEC 60870-5-104 addresses for the gateway to the control center. Per the catalog it draws on engineering experience from over 500,000 devices. Flexible engineering offers custom naming and structure for logical nodes while keeping the user's own language (for example, distance protection with its zones rather than a group of nodes).

SIPROTEC DigitalTwin: your device in the cloud

The digital twin is a virtual copy of a real SIPROTEC 5 device with its algorithms, functions and communication interfaces, running in the cloud, available around the clock from anywhere and without hardware.

  • Injecting static currents and voltages, simulating binary inputs, and operating the device through its display and keys.
  • Testing protection with static values, COMTRADE output or the state sequencer, and replaying a fault record.
  • Integration with SCADA systems and the IEC 61850, DNP3, Modbus TCP and IEC 104 protocols, and GOOSE between devices.
  • Security functions such as Syslog, RADIUS and RBAC.
  • Continuous training in a virtual environment close to real system conditions.

The stated benefits: lower investment in test equipment (CAPEX), lower operating cost (OPEX) thanks to better upfront testing that includes patches, and faster analysis of faults by reproducing product and system behavior.

SIGRA: analysis after the fault

After an incident on the grid, quick and complete fault analysis is vital to cut outage time. SIGRA displays COMTRADE records in 6 diagram types: time signals, circle diagrams (such as R/X), phasor diagrams, bar charts (for harmonics), tables, and fault location. It calculates additional quantities such as impedances, powers and symmetrical components, supports two synchronized cursors, merging records from both line ends by drag and drop on a common time base, and offline fault location.

SIPROTEC Dashboard and GridEdge

SIPROTEC 5 connects to the substation automation level and to the SICAM GridEdge node, and from there to the cloud, which separates field devices from the cloud for security. The Dashboard gives crews access to fault records and event logs even before they travel to the site, and shows maps, substations and device data, breaker I²t statistics and transformer hot-spot measurements, with comparison of firmware versions and monitoring of settings at substation or grid level.

✅ Part 10 takeaways
  • DIGSI 5 brings engineering and testing into one tool, in three editions: Compact, Standard and Premium.
  • The Test Suite simulates inputs inside the device, reducing the need for secondary test sets.
  • DigitalTwin lets you test devices and systems in the cloud without hardware.
  • SIGRA and the Dashboard turn fault records into faster decisions.

Reference table: functions by ANSI number

ANSIFunctionPart
14Locked rotor4
24Overexcitation V/f5
25Synchrocheck / synchronization5
27Undervoltage5
32 / 32RPower / reverse power5
37Undercurrent / minimum power4, 5
38Temperature supervision (RTD)4
46Unbalanced load4
47Negative-sequence overvoltage5
48Starting-time supervision4
49 / 49RThermal overload (stator / rotor)4
50/51Phase overcurrent2
50N/51NGround overcurrent2
50Ns/51NsSensitive ground fault3
50HSInstantaneous high-current tripping2
SOTFSwitch-onto-fault2
50BFBreaker failure2
50LLoad jam4
50RSBreaker restrike monitoring4
51VVoltage-dependent overcurrent2
59 / 59NOvervoltage / residual voltage5
59CCapacitor peak overvoltage4
60CCapacitor current unbalance4
60FLMeasuring-voltage failure2
66Motor restart inhibit4
67 / 67NDirectional overcurrent2
67NsDirectional sensitive ground fault3
74TCTrip-circuit supervision2
79Automatic reclosing2
81 / 81UFrequency, underfrequency load shedding, df/dt5
86Lockout2
87NRestricted ground fault3
FLFault locator5

Glossary

TermMeaning
Application templateA ready-made DIGSI 5 template holding the basic functions and settings for a given application.
Function pointA license unit spent to enable additional functions from the function library.
CFCContinuous Function Chart: a graphical logic editor for automation and interlocking.
GOOSEFast IEC 61850 messages that exchange signals between devices instead of wires.
MMSThe client/server channel of IEC 61850 for reports, control and settings.
SCLThe IEC 61850 substation configuration language (ICD, CID, SCD files…).
RedBoxA coupling unit that joins HSR with PRP or with an ordinary network.
COMTRADEA standard format for exchanging fault records.
RBACRole-based access control with central user management.
SyslogA protocol for sending event logs to a central server.
PMU / synchrophasorPhasor measurement with high time accuracy for grid-stability monitoring (under development in this release).
InrushMagnetizing inrush current when a transformer is energized.
3I0Zero-sequence current (three times I0).
Life contactAn output that indicates device health and opens when the device is isolated.
MLFBThe order number that can be transferred straight into DIGSI 5.
DigitalTwinA cloud virtual copy of the device for testing without hardware.

Frequently asked questions

Click a question to reveal the answer
Is 7SX800 suitable for high voltage?
The catalog says it is aimed mainly at medium voltage, but it can also be used in low- and high-voltage applications.
Can the device hardware be expanded?
No, the hardware is not modular; you choose the right variant from the start.
How do I add a function after ordering?
From the function library in DIGSI 5, as long as you do not exceed your available function points; extra points can be ordered.
Does it support IEC 61850 Edition 2?
Yes, the catalog states full compatibility with editions 1, 2.0 and 2.1.
Can I test my settings without a device?
Yes, through SIPROTEC DigitalTwin, or by testing CFC charts offline in DIGSI 5.
Is IEEE 1588 synchronization available?
Per the catalog it is under development; IRIG-B, SNTP and others are available today.
📌 Closing note
The idea that ties everything together: one small device, shaped by software and the functions you need, and tested and analyzed with integrated tools. Always start from the application (feeder? motor? renewable connection?), then choose the template, then the variant, then the function points.
Source: Siemens catalog "SIPROTEC 5 Compact – 7SX800", Edition 5 (from V9.50). This article is an educational explanation in the author's own words; values and specifications are for guidance only, so always check the latest catalog and device manual before any design or order. This blog is not affiliated with Siemens. SIPROTEC, DIGSI and SIGRA are trademarks of their owners.