From Drawing to Commissioning: DIGSI 5, Built-in Testing, SIPROTEC DigitalTwin and SIGRA

عنوان المقال
From Drawing to Commissioning: DIGSI 5, Built-in Testing, SIPROTEC DigitalTwin and SIGRA
A great relay deserves great engineering tools. Meet the whole project journey with DIGSI 5 and its companions.
Part 10 of 10⏱ 5 min readLevel: Intermediate
🎯 What you will learn in this part
  • The project stages and the tool for each
  • DIGSI 5, its editions and its main editors
  • Built-in testing, DigitalTwin and fault analysis with SIGRA

The integrated workflow

Engineering in SIPROTEC 5 Compact is organized around a workflow: from the single-line diagram of the primary system, through ordering, engineering and settings, to testing and commissioning. The catalog divides it into five stages: project definition, device engineering, system engineering, commissioning, and operation and service.

ToolRole
DIGSI 5The configuration, commissioning and operation tool for all SIPROTEC 5 devices.
IEC 61850 System ConfiguratorVendor-independent IEC 61850 substation engineering.
Web MonitorA browser interface for commissioning and monitoring.
SIPROTEC DigitalTwinA cloud virtual twin of the device for testing without hardware.
SIGRAAnalysis of fault records (COMTRADE).
SIPROTEC DashboardA view of the protection fleet through GridEdge and the cloud.

DIGSI 5: everything in one project

In DIGSI 5 all device components and data are managed in one project: topology, devices, setting values, communication settings and process data. You can take the order number (MLFB) from the configurator and create the device with it directly, so engineering starts on a consistent basis.

EditionIn short
CompactFor small projects of up to 8 devices (Compact or non-modular) or one modular device; includes the CFC editor, the device display editor and built-in testing; needs no license key.
StandardNo limit on the number of devices; includes the IEC 61850 System Configurator and single-line and network-topology editors; SIGRA is optional.
Premium with SIGRALike Standard, with flexible IEC 61850 engineering and functional naming, and it includes SIGRA.

The most important DIGSI 5 editors

  • Single-Line Editor: define the initial substation layout with a library of ANSI and ISO symbols, link protection elements to breakers and current and voltage transformers, and take transformer ratios from it automatically.
  • Display Editor: turn the single-line diagram into a device display, with a symbol editor to create your own symbols.
  • Information Routing: an Excel-like routing matrix to link signals to inputs, outputs, LEDs and logs, with powerful filters.
  • Communication Mapping: presets for each protocol that you can edit and copy between devices.
  • CFC: a graphical logic editor with macros, offline testing and online monitoring.

Three ways to view settings

The parameter editor lets you view settings as primary values (so you do not need transformer ratios and avoid conversion errors), as per-unit values, or as secondary values. Protection curves are shown graphically so you can immediately check the effect of your change, parameter groups can be compared in one window, and favorite parameters can be marked for quick display.

💡 Teamwork
Thanks to export and import functions, one team member can set the protection parameters, another the routing and a third the system-interface parameters, and the sections are then merged. DIGSI 5 supports open formats such as IEC 61850 formats and TEA-X.

Test Suite: testing without secondary test sets

  • The built-in test sequencer: you build a test sequence (a short circuit, for example) with up to 6 test items and load it into the device, which simulates the analog and binary inputs in real time.
  • Hardware and wiring test: reading input states, driving contacts and LEDs, and showing measured values on phasor diagrams to find reversed connections, vector-group errors or directionality problems.
  • A wiring test between devices over Ethernet, with no helper needed at the neighboring substation.
  • A loop test for communication links, and finally a protocol test to send chosen values toward SCADA.
  • Offline CFC debugging to test charts before the device arrives.

The result, per the catalog: much shorter testing and commissioning time, documentation of every test performed, and no need for most testing with secondary test sets.

Web Monitor: a browser instead of software

A web interface built into the device that works through the browser, locally or remotely. It helps during commissioning to inspect and compare settings between two devices or against the Siemens default, during inspection to view values with their minimum, maximum and average, and during operation.

IEC 61850 System Configurator

A vendor-independent interactive engineering tool that supports Siemens and other devices and all SCL file types (ICD, IID, CID, SCD, SSD and SED). It supports editions 1, 2.0 and 2.1, and covers GOOSE, reports, system topology, SMV for the process bus, and IEC 60870-5-104 addresses for the gateway to the control center. Per the catalog it draws on engineering experience from over 500,000 devices. Flexible engineering offers custom naming and structure for logical nodes while keeping the user's own language (for example, distance protection with its zones rather than a group of nodes).

SIPROTEC DigitalTwin: your device in the cloud

The digital twin is a virtual copy of a real SIPROTEC 5 device with its algorithms, functions and communication interfaces, running in the cloud, available around the clock from anywhere and without hardware.

  • Injecting static currents and voltages, simulating binary inputs, and operating the device through its display and keys.
  • Testing protection with static values, COMTRADE output or the state sequencer, and replaying a fault record.
  • Integration with SCADA systems and the IEC 61850, DNP3, Modbus TCP and IEC 104 protocols, and GOOSE between devices.
  • Security functions such as Syslog, RADIUS and RBAC.
  • Continuous training in a virtual environment close to real system conditions.

The stated benefits: lower investment in test equipment (CAPEX), lower operating cost (OPEX) thanks to better upfront testing that includes patches, and faster analysis of faults by reproducing product and system behavior.

SIGRA: analysis after the fault

After an incident on the grid, quick and complete fault analysis is vital to cut outage time. SIGRA displays COMTRADE records in 6 diagram types: time signals, circle diagrams (such as R/X), phasor diagrams, bar charts (for harmonics), tables, and fault location. It calculates additional quantities such as impedances, powers and symmetrical components, supports two synchronized cursors, merging records from both line ends by drag and drop on a common time base, and offline fault location.

SIPROTEC Dashboard and GridEdge

SIPROTEC 5 connects to the substation automation level and to the SICAM GridEdge node, and from there to the cloud, which separates field devices from the cloud for security. The Dashboard gives crews access to fault records and event logs even before they travel to the site, and shows maps, substations and device data, breaker I²t statistics and transformer hot-spot measurements, with comparison of firmware versions and monitoring of settings at substation or grid level.

✅ Key Takeaways
  • DIGSI 5 brings engineering and testing into one tool, in three editions: Compact, Standard and Premium.
  • The Test Suite simulates inputs inside the device, reducing the need for secondary test sets.
  • DigitalTwin lets you test devices and systems in the cloud without hardware.
  • SIGRA and the Dashboard turn fault records into faster decisions.
🧠 Test yourself (click a question to reveal the answer)
Which edition includes the IEC 61850 System Configurator?
Standard and Premium (with SIGRA in Premium).
What does DigitalTwin add?
Virtual cloud testing of the device and the system, 24/7, from anywhere, without hardware.
Which fault-record format does SIGRA analyze?
COMTRADE.
Source: Siemens catalog "SIPROTEC 5 Compact – 7SX800", Edition 5 (from V9.50). This article is an educational explanation in the author's own words; values and specifications are for guidance only, so always check the latest catalog and device manual before any design or order. This blog is not affiliated with Siemens. SIPROTEC, DIGSI and SIGRA are trademarks of their owners.