High-Resistance Earth Faults: Earth Fault Protection in Earthed and Non-Earthed Systems

High-Resistance Earth Faults: Earth Fault Protection in Earthed and Non-Earthed Systems
Distance protection may not see an earth fault through a large resistance. This is where earth current protection comes in.
Part 7 of 10⏱ 4 min readLevel: Intermediate to advanced
🎯 What you will learn in this part
  • Earth fault stages, direction and stabilization
  • Earth fault protection with teleprotection
  • Earth fault detection in non-earthed systems

Earth fault protection in earthed systems (optional)

This protection is intended for high-resistance earth faults, where distance protection may not pick up. It is a staged earth overcurrent protection:

  • Up to 3 definite-time (DT) stages and one inverse-time (IDMT) stage with characteristics from several standards, and a fourth definite-time stage can be set for the IDMT stage.
  • High sensitivity from 3 mA (depending on the version).
  • Phase current stabilization against CT saturation errors.
  • Inrush stabilization using the second harmonic.
  • Tripping time dependent on the zero-sequence voltage.
  • Each stage can be non-directional, or directional forward or reverse.
  • Instant tripping when closing onto a fault from any stage.

Direction determination methods

MethodQuantities used
Zero-sequenceI0 and U0
Zero-sequence with transformer star-point currentI0 and IY
Negative-sequenceI2 and U2

Teleprotection for earth faults

One or more earth fault stages can work together with a signal transmission scheme, also suited to lines with three ends. The schemes: directional comparison, directional unblocking and directional blocking, with measures for weak or zero infeed (echo) and transient blocking. The result is fast tripping from both ends for high-resistance earth faults along the whole line.

Isolated and resonant-earthed networks

In these networks earth fault current is small, so 7SA6 (in sensitive-detection versions) provides a dedicated detection function:

  • Detection of the displacement voltage.
  • Determination of the earth-faulted phase.
  • Sensitive determination of earth fault direction.
  • Phase displacement correction for current transformers.
  • Logging of up to 8 earth faults in devices with sensitive earth fault detection.
📌 The sensitive current input
In sensitive versions the sensitive earth current input withstands 300 A for 1 s, 100 A for 10 s and 15 A continuously, and burdens about 0.05 VA.
💡 A design point
Choose the device version (earth fault protection, sensitive detection, or both) from the start, since it is defined in the order code and cannot be added later.
✅ Key Takeaways
  • Earth fault protection complements distance protection for high-resistance faults.
  • 3 definite-time stages + 1 inverse-time stage, with sensitivity down to 3 mA.
  • Direction by I0/U0, I0/IY or I2/U2.
  • Non-earthed networks get sensitive detection with displacement voltage, phase and direction determination.
🧠 Test yourself (click a question to reveal the answer)
What is the lowest sensitivity of the earth fault protection?
From 3 mA, depending on the version.
Which quantities does the device use to determine earth fault direction?
I0 and U0, or I0 and IY, or I2 and U2.
How many earth faults does the device log?
Up to 8, in versions with sensitive detection.
Source: Siemens manual "SIPROTEC Distance Protection 7SA6" (C53000-G1176-C156, Siemens copyright 2000 and 2002). This article is an educational explanation in the author's own words; values are for guidance only, so check the manual for your installed version before any design or setting. This blog is not affiliated with Siemens. SIPROTEC and DIGSI are trademarks of their owners.