A relay without self-monitoring can fail silently. See how 7SA6 supervises itself and records everything.
Part 9 of 10⏱ 4 min readLevel: Intermediate
🎯 What you will learn in this part
- Self-monitoring of hardware and measured values
- Logs, fault recording and time synchronization
- Control, interfaces and protocols
Monitoring from the input to the output relay
The device monitors itself from the measuring inputs to the command relays; monitoring circuits and the processor check the hardware for faults and inadmissible states. Examples:
- The 5 V processor voltage is monitored by hardware; if it drops, the device is taken out of service and restarted when the voltage recovers.
- Failure or switch-off of the auxiliary supply is alarmed by a normally closed contact (changeable to normally open by a jumper).
- The offset and reference voltage of the A/D converter: an inadmissible deviation blocks the protection and permanent faults are alarmed.
- The charge of the buffer battery (alarm Fail Battery), which keeps the clock, counters and alarms during supply loss.
Supervising the instrument transformer circuits
The secondary circuits of current and voltage transformers are largely covered by summation and symmetry checks, with checks of the load impedance, measured direction and phase sequence. If measured voltage is lost the device reverts to emergency overcurrent (Part 4). Trip circuit supervision is available using the binary inputs, with group alarms and defined responses for each failure type.
Logs and recording
| Item | Capacity or property |
|---|---|
| Event log | Operating messages. |
| Trip log | Fault messages for the last 8 network faults, with 1 ms resolution. |
| Earth fault log | Records for up to 8 earth faults (devices with sensitive detection). |
| Fault recorder (oscillography) | Analog and user-configurable binary traces with a maximum time range of 15 seconds. |
| Switching statistics | Number of trip and close commands, fault data and interrupted currents. |
Instantaneous values during the fault are stored for later analysis, and messages are not lost on supply failure thanks to the battery.
Control and command processing
- Switching breakers manually via the local keys, configurable function keys, the system interface (such as SICAM or LSA) or DIGSI 4.
- Feedback on switching state from the breaker auxiliary contacts.
- Plausibility check of breaker positions and interlocking conditions before any operation.
- User-defined logic with the CFC editor: logic functions, time delays and set-point interrogation.
- A default display and, in some versions, a single-line feeder diagram.
Communication
| Interface | Details |
|---|---|
| Front RS232 | 9-pin socket for a PC; 4800 to 115200 baud (default 38400, 8E1), up to 15 m. |
| Service | RS232, RS485 or optical, for remote operation by modem or a central station, DIGSI 4 required. |
| System | For connection to the control centre; IEC 60870-5-103, or PROFIBUS FMS (per the manual). |
| Time synchronization | A battery-backed clock synchronized via IRIG-B, DCF77, a binary input or the system interface. |
💡 Worth noting
This device's protocols are from the SIPROTEC 4 generation, with a narrower list than the newer generation. If you plan to integrate it into a modern system, check the protocol list in Appendix A.5 of the manual.
✅ Key Takeaways
- Comprehensive monitoring: supply, A/D converter, battery and instrument-transformer circuits.
- A trip log of the last 8 faults and recording of up to 15 seconds.
- Local and remote control with interlock checks and feedback, and logic programmed in CFC.
- Interfaces: front, service and system, with IRIG-B or DCF77 synchronization.
🧠 Test yourself (click a question to reveal the answer)
How many faults does the trip log hold?
The last 8 network faults.
What is the maximum range of the fault recorder?
15 seconds.
What software is needed for the front and service interfaces?
DIGSI 4.
🧭 Series map
1 Overview of the relay2 Measuring loops, pickup and polygon3 Zones, tripping logic and compensation4 Power swing and backup overcurrent5 Teleprotection and weak infeed6 Protection data interface and topology7 Earth fault protection8 The supporting functions9 Monitoring, recording and communication10 Hardware and commissioningComing next: from crate to commissioning: hardware, technical data and commissioning steps.
📚 Read the complete reference guide: the whole series in one articleSource: Siemens manual "SIPROTEC Distance Protection 7SA6" (C53000-G1176-C156, Siemens copyright 2000 and 2002). This article is an educational explanation in the author's own words; values are for guidance only, so check the manual for your installed version before any design or setting. This blog is not affiliated with Siemens. SIPROTEC and DIGSI are trademarks of their owners.